UPS runtime chart
Estimated runtime for common UPS battery setups, using sealed lead-acid (AGM) batteries in good condition, 85% inverter efficiency, and the UPS shutting down at about 80% of the battery’s capacity.
| UPS battery | 50 W | 100 W | 200 W | 400 W |
|---|---|---|---|---|
| 1 × 12 V 7 Ah (small 600–850 VA UPS) | 46 min | 21 min | 9 min | 4 min |
| 1 × 12 V 9 Ah (1000 VA) | 1 h 2 min | 28 min | 13 min | 6 min |
| 2 × 12 V 9 Ah (1500 VA) | 2 h 17 min | 1 h 2 min | 28 min | 13 min |
| 2 × 12 V 18 Ah (2000–3000 VA) | 5 h 3 min | 2 h 17 min | 1 h 2 min | 28 min |
Doubling the load more than halves the runtime. A 7 Ah battery at 400 W is discharging at several times its rated current, and lead-acid delivers far less of its rated capacity that fast.
How to find your UPS load in watts
- Read the UPS display or software. Most units show the load in watts or as a percentage of capacity. Multiply the percentage by the UPS watt rating (not the VA).
- Use a plug-in power meter on each device for a few minutes of normal use.
- Estimate from typical values: a cable modem and Wi-Fi router draw 10–25 W together, a laptop 30–90 W, an office desktop with monitor 100–250 W, and a gaming PC 300–600 W under load.
How UPS runtime is calculated
The calculator turns the battery into watt-hours (Ah × V × number of batteries), takes off the inverter loss inside the UPS, and applies Peukert’s law for sealed lead-acid batteries. That last step matters more for a UPS than for almost any other battery: UPS batteries are small and the loads are large compared to them, so they routinely discharge in 10 to 30 minutes, where a lead-acid battery gives well under its 20-hour rating. The full method is on how battery runtime is calculated.
Planning a bigger backup for a home office or network rack? Use the battery size calculator to work out the capacity for the hours you need, or compare with a portable power station.